Finding Description
**NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on Service Agreement review, policy review, observation, and interview, the facility failed to provide effective housekeeping services and maintenance services to maintain a sanitary, orderly, and comfortable environment as evidenced by missing ceiling tiles, missing grout in tiles, brown debris and brownish and black build-up on the floors and in corners of rooms, unpainted, exposed plaster, brownish build-up on window ledges, blinds, and air conditioners, air conditioners with missing pieces, discolored grout in bathrooms, worn linoleum floors exposing subflooring, gray areas on ceiling tiles, unclean, broken and rust colered resident equipment, unclean exhaust fans, brown substance and stains in sinks and on commodes, holes in walls, loose and broken tiles and base boards, bulging and crumbling dry wall, odors, gouged and scratched walls, peeling paint; corroded faucets, missing covers on lights, an improperly hanging door, and mismatched floor tiles in 44 of 57 (101, 102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 112, 113, 114, 115, 117, 118, 119, 121, 122, 123, 124, 125, 126, 128, 130, 219, 220, 221, 225, 226, 227, 228, 230, 231, 232, 233, 234, 235, 241, 244, 245, 246, and 247) resident rooms observed.
The facility's failure to provide effective housekeeping services and maintenance services to maintain a sanitary, orderly and comfortable environment resulted in Substandard Quality of Care.
The Extended Survey was conducted on 6/26/19.
The findings include:
1. The facility's HOUSEKEEPING/LAUNDRY SERVICE AGREEMENT dated January 1, 2011 and signed 1/6/11 and 1/10/11, documented, .[Named Corporation] will provide .Monthly unit inspections and regular District Manager visits .
The (Named Corporation) Housekeeping Procedures policy with a revision date of 6/2016, documented .BATHROOM CLEANING .Dust mop. Pick up trash .Sanitize sinks .Sanitize commode, tank, bowl and base. Use brush for inside of bowl .Spot clean - Walls .Damp mop .Clean vents .DAILY PATIENT ROOM CLEANING .With a cloth & [and] disinfectant wipe all horizontal (flat) surfaces .spot clean all vertical surfaces .Use dust mop and gather all trash and debris .Damp mop floor .Every room to be cleaned is that resident's home .COMPLETE ROOM CLEANING .Every room must be Deep Cleaned at least 1x [time]/[per] month .
2. Observations on the 100 Hall on 6/24/19 beginning at 4:42 PM, 6/25/19 beginning at 8:22 AM, 1:50 PM, and 3:20 PM revealed the following:
a. room [ROOM NUMBER] - A missing ceiling tile, missing grout around the edge of the floor tile in the bathroom, a black substance in the corners of the room, and unpainted, exposed plaster.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:22 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor confirmed the missing ceiling tile and the missing grout around the edge of the floor tile in the bathroom. The Maintenance Supervisor looked at the unpainted, exposed plaster and stated, Needs some paint. The Housekeeping District Manager was asked if the black substance should be present in the corners of the room. He stated, No, Ma'am .
b. room [ROOM NUMBER] - [NAME] debris on the floor in the corner behind the door, pictures in the floor behind the first bed, brown build-up in the air conditioner, plastic pieces of the air conditioner unit were missing, and the flooring was worn away exposing some of the subflooring next to the wall in the room, and a black substance in the grout in the bathroom.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:24 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor was not clean. The Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, Part of this is broken off .no. The Maintenance Supervisor was asked if the black substance in the grout and the exposed subflooring should be present. The Maintenance Supervisor stated, No.
c. room [ROOM NUMBER] - Areas in the linoleum were worn, exposing the subflooring, and a sticky film was covering the floor.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:26 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if the floor was clean and in good repair. He stated, No, it's old and torn. The Administrator was asked if the linoleum should be worn exposing the subflooring. He stated, No.
d. room [ROOM NUMBER] - Worn areas in the linoleum that exposed a large amount of the subflooring, and brown build-up on the blinds and the air conditioner.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:29 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if the blinds and the floor were clean and in good repair. The Housekeeping District Manager confirmed the blinds were not clean and stated, Those are holes in the linoleum. The Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No.
e. room [ROOM NUMBER] - [NAME] debris behind the door and in the corners of the room.
f. room [ROOM NUMBER] - [NAME] debris in the corners of the room.
g. room [ROOM NUMBER] - A brown build-up on the air conditioner, a gray discoloration on the ceiling tile in the bathroom, a broken armrest on a raised toilet seat in the bathroom, and a thick layer of blue masking tape covering the bathroom door handle.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:35 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor confirmed the air conditioner was not clean and confirmed the gray discoloration on the ceiling in the bathroom. The Maintenance Supervisor was asked if residents should use broken raised toilet seats. The Maintenance Supervisor stated, No. The Maintenance Supervisor removed the layers of blue masking tape and stated, .that shouldn't be there .
h. room [ROOM NUMBER] - A brown build-up on the air conditioner, and a rectangular piece of wood lying on the floor behind the resident's bed.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:37 PM, in room [ROOM NUMBER], revealed the Maintenance Supervisor confirmed the air conditioner was not clean. The Maintenance Supervisor was asked why a wooden board was lying on the floor behind the resident's bed. The Maintenance Supervisor stated, To keep them from knocking the bed into the wall.
i. room [ROOM NUMBER] - [NAME] debris on the window ledge, brown build-up on the air conditioner, a bracket missing from the air conditioner unit with wires exposed. The commode tank was covered with an incomparable lid that did not properly fit over the tank, exposing the tank, and debris on the exhaust fan in the bathroom
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:39 PM, in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor was not clean. The Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No .it needs to be bolted to the wall. The Maintenance Supervisor confirmed the commode tank lid was not the appropriate size, and confirmed the exhaust fan was not clean.
j. room [ROOM NUMBER] - [NAME] debris on the floor throughout the room.
k. room [ROOM NUMBER] - [NAME] debris along the baseboard throughout the room.
l. room [ROOM NUMBER] - Scattered brown debris on the floor and in the corners, a call light and call light cord were covered in a brown substance. The vinyl baseboard was missing and the dry wall was exposed and rough with pieces of dry wall in the floor.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:43 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor was not clean. The Housekeeping Manager was asked if the call light was clean. The Housekeeping District Manager stated, No. The Maintenance Supervisor was asked if there should be missing vinyl cove base molding and crumbling dry wall. The Maintenance Supervisor stated, No.
m. room [ROOM NUMBER] - Rust colored build-up on the overbed table, and scattered brown debris on the floor and in the corners of the room.
n. room [ROOM NUMBER] - Rust colored build-up on the overbed table, and scattered brown debris on the floor throughout the room.
o. room [ROOM NUMBER] - Scattered brown debris on the floor throughout the room.
p. room [ROOM NUMBER] - [NAME] debris scattered on the floor throughout the room, brown spots on the floor in front of the closet, a dead fly, and brown debris on the window ledge.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:46 PM in room [ROOM NUMBER], the Housekeeping District Manager was asked if the floor and window ledge were clean. The Housekeeping District Manager stated, No.
q. room [ROOM NUMBER] - The base of an overbed table had brown build-up, brown stains in the toilet, and a hole in the wall in the bathroom where a paper towel holder previously had been on the wall.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:48 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if the overbed table base should be not be clean and if there should be brown stains in the toilet. The Housekeeping District Manager stated, No. The Administrator looked at the hole in the bathroom wall and stated, Who did that? Gees!
r. room [ROOM NUMBER] - Grayish-black areas on the floor throughout the room
s. room [ROOM NUMBER] - Grayish-black areas on the floor throughout the room near the bed, peeling paint and damaged exposed drywall on the wall behind the first bed, a large, round, gray area on the ceiling, brown stains in the toilet, a corroded sink faucet, and a black substance scattered on the bathroom floor.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:55 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floors in the room and bathroom were not clean and confirmed the brown stains in the toilet. The Maintenance Supervisor confirmed the large, round, gray area on the ceiling and looked at the sink faucet and stated, It is corroded. The Maintenance Supervisor was asked if the peeling paint and damaged exposed drywall were acceptable. The Maintenance Supervisor stated, No.
t. room [ROOM NUMBER] - [NAME] build-up on the air conditioner and the vented front of the air conditioner was loose. There were large, round, gray areas on 2 bulging ceiling tiles with in the bathroom, a musty smell in the bathroom, a large area of bulging dry wall behind the commode, and no cover on the bathroom light, exposing a bare light bulb.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 4:07 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No. The Housekeeping District Manager walked in the bathroom and stated, .smells musty. The Maintenance Supervisor confirmed the bulging ceiling tiles on the bathroom ceiling tiles and the bulging dry wall and stated, It has been wet at one time. The Maintenance Supervisor confirmed there should be a cover over the light bulb.
u. room [ROOM NUMBER] - The linoleum floor near the first bed was worn exposing a large area of subfloor. There were brown substances on the floor throughout the room, a brown build-up on the air conditioner, and a loose screw lying on the window ledge.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 4:05 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if the floor was clean and in good repair. The Housekeeping District Manager stated, No. The Maintenance Supervisor confirmed the air conditioner was not clean and looked at the screw and stated, .doesn't need to be there.
v. room [ROOM NUMBER] - areas of a brownish substance on the floor throughout the room, an odor in the room, large, round, gray areas on the ceiling tile, and dry wall bulging up on the wall beside the commode.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:52 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor was not clean. The Maintenance Supervisor stated, It doesn't smell very clean. The Maintenance Supervisor confirmed the gray areas on the ceiling tile and the dry wall bulging up beside the toilet and stated, It's been wet. The Administrator touched the wall and confirmed it felt damp.
w. room [ROOM NUMBER] - Areas of a brown build-up on the floor throughout the room and a dried, red substance on the floor near the bed, a brown build-up on the blinds and on the air conditioner and plastic parts of the air conditioning unit missing. There was veneer missing down the front right side of the 3 drawer bedside chest, no cover on the bathroom light, exposing a bare light bulb, and a corroded sink faucet.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 4:02 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor and the blinds were not clean. The Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No. The Maintenance Supervisor was asked if the 3 drawer chest was in good repair. The Maintenance Supervisor said, No. The Maintenance Supervisor confirmed that a cover was needed over the bathroom light bulb and confirmed the sink faucet was corroded.
x. room [ROOM NUMBER] - Areas of brown build-up on the floor throughout the room and on the air conditioner and the air conditioning unit was not securely attached to the wall. The drywall was bulging on the wall to the right of the bathroom commode.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:57 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor was not clean. The Maintenance Supervisor confirmed the drywall was bulging and stated, [It was due to] a leaky roof. The Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No, and confirmed it should be securely attached to the wall.
y. room [ROOM NUMBER] - A metal office chair with the back rest of the chair missing, and the seat was torn with jagged edges of material, exposing the inner foam.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 3:59 PM in room [ROOM NUMBER], revealed the Administrator looked at the chair and stated, It should be thrown out.
z. room [ROOM NUMBER] - Areas of brown build-up on the floor mats in the room and brown build-up on the air conditioner. There were plastic pieces missing from the air conditioning unit, 2 holes in the wall above the bed, and the dry wall was bulging beside the air conditioner.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 4:09 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if the floor mats were clean. The Housekeeping District Manager stated, I don't think so . The Maintenance Director was asked if the air conditioner was clean and in good repair. The Maintenance Director stated, No. The Maintenance Director was asked if the dry wall should be bulging next to the air conditioner and should there be holes in the wall. The Maintenance Director stated, No.
3. Observations on the 200 Hall on 6/24/19 beginning at 9:20 AM and 4:22 PM, and on 6/25/19 beginning at 8:02 AM and 4:43 PM revealed the following:
a. room [ROOM NUMBER] - Yellowish brown stains in the sink.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 4:45 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if there should be stains in the sink. The Housekeeping District Manager stated, No .
b. room [ROOM NUMBER] - Areas of brown build-up on the floor throughout the room.
c. room [ROOM NUMBER] - Areas of brown build-up on the floor throughout the room, a dried white substance on the mirror, and a brown substance smeared on the commode.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 4:50 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if the mirror and commode were clean. He stated, No. The Housekeeping District Manager was asked if the floor was clean. He stated, .wax build-up.
j. room [ROOM NUMBER] - [NAME] build-up on the blinds and the air conditioner. The commode seat was loose and falling off the commode in the bathroom.
k. room [ROOM NUMBER] - [NAME] build-up on the air conditioner. The entire front vented section of the air conditioning unit was missing exposing the inner contents of the air conditioner, and brown build-up on the blinds.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:15 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No. The Housekeeping District Manager confirmed the blinds were not clean.
l. room [ROOM NUMBER] -Areas of brown build-up on the floor throughout the room, brown build-up on the blinds, broken blinds, brown build-up on the window ledge and on the air conditioner.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:17 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor, blinds, and window ledge were not clean. The Housekeeping District Manager was asked if the blinds were in good repair. He stated, No, they are broken. The Maintenance Supervisor confirmed the air conditioner was not clean.
m. room [ROOM NUMBER] - An exposed pipe under the sink that was wrapped in bright orange foam and black duct tape, 2 broken tiles lying under the sink on the floor, brown build-up on the blinds, and broken blinds on the windows.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:21 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor was asked if there should be exposed pipe under the sink covered in bright orange foam and black duct tape. The Maintenance Supervisor stated, No. The Maintenance Supervisor was asked if tiles should be falling off the wall and lying on the floor. The Maintenance Supervisor stated, No. The Housekeeping District Manager was asked if the blinds were clean and in good repair. The Housekeeping District Manager stated, No.
n. room [ROOM NUMBER] - Areas of a brown substance on the floor throughout the room, brown build-up on the blinds and on the air conditioner, and plastic parts of the air conditioning unit were missing.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:27 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor and blinds were not clean. The Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No.
o. room [ROOM NUMBER] - Areas of a brown substance on the floor throughout the room, brown build-up on the window ledge and on the air conditioner, and the floor tiles did not match.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:30 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor and window ledge were not clean. The Administrator confirmed the floor tiles did not match and stated, It's not homelike.
p. room [ROOM NUMBER] - A strong odor in the room, brown build-up on the air conditioner and plastic parts of the air conditioning unit were missing.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:30 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager stated, Smells like urine in here. The Maintenance Supervisor was asked if the air conditioner was clean and in good repair. The Maintenance Supervisor stated, No.
q. room [ROOM NUMBER] - Peeling paint and broken, bulging drywall between the bathroom and sink.
r. room [ROOM NUMBER] - The drywall in the bathroom was bulging. There was a brown stain on the wall next to the toilet. The tile was separating from the wall in the bathroom, and there were stains in the commode.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:00 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor was asked if there should be bulging dry wall, stained walls, and tiles separating from the wall. The Maintenance Supervisor stated, No. The Housekeeping District Manager confirmed the commode was not clean.
s. room [ROOM NUMBER] - There was a hole approximately the circumference of an empty toilet paper roll above the toilet in the bathroom that was covered with a toilet paper roll to hide the insulation.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:05 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor was asked if there should be a hole in the bathroom wall, exposing insulation, with a toilet paper roll covering it. The Maintenance Supervisor stated, No.
t. room [ROOM NUMBER] - Areas of a brown substance on the floor throughout the room, several tiles separating from the base of the bathroom wall near the floor, and dry wall bulging in the bathroom.
u. room [ROOM NUMBER] - The entry door was scraping the floor when opened or closed, making it difficult to open and close the door.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:10 PM in room [ROOM NUMBER], revealed the Administrator confirmed the door needed to be readjusted.
v. room [ROOM NUMBER] - [NAME] stains in the commode, brown build-up in the bathroom sink.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 4:55 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager was asked if there should be brown stains in the toilet and brown build-up in the bathroom sink. The Housekeeping District Manager stated, No.
w. room [ROOM NUMBER] - Areas of a brown substance on the floor throughout the room and in the corners of the room, brown build-up on the blinds, a brown stain in the sink, several loose tiles in the bathroom floor, and large brown stains on the ceiling tiles.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:30 PM in room [ROOM NUMBER], revealed the Housekeeping District Manager confirmed the floor and corners were not clean, and the sink was stained. The Maintenance Supervisor was asked if there should be large brown stains on the ceiling tiles. The Maintenance Supervisor stated, No.
x. room [ROOM NUMBER] - There was brown build-up on the air conditioner. The bathroom sink faucet was rusted, and there was a brown stain in the commode.
Interview with the Administrator, Housekeeping District Manager, and the Maintenance Supervisor on 6/25/19 at 5:32 PM in room [ROOM NUMBER], revealed the Maintenance Supervisor confirmed the air conditioner was not clean. The Maintenance Supervisor was asked if the faucet should be rusted. He stated, No. The Housekeeping District Manager was asked if the toilet should have brown stains. The Housekeeping District Manager stated, No.
3. Interview with the Housekeeping District Manager on 6/26/19 at 11:20 AM, in the Conference Room, revealed the Housekeeping District Manager stated he took over this facility in May. The Housekeeping District Manager was asked what problems he had identified in May. He stated, .build up on the floors .walls, dirt build up .cleaning schedules weren't being followed, no systems in place .the quality control inspection was not being followed .
Interview with the Administrator on 6/26/19 at 5:15 PM, in the Conference Room, revealed the Administrator stated that he had been in the administrative position since October 2018. The Administrator was asked what problems he had identified in October. He stated, Flooring, roof, rooms, it was dirty .problems were here for years .rooms were in bad shape .they still look bad, roof has to get fixed .flooring .don't even like to look at it, we know it's got to come out . The Administrator was asked why these problems have not been addressed. The Administrator stated, .corporate .approval process .
Interview with the Maintenance Supervisor on 6/27/19 at 9:41 AM, in the Conference Room, revealed the Maintenance Supervisor was asked what problems he had identified in the building. He stated, .we have a lot of issues with the roof, the ceiling, with them being wet .we've got pinholes everywhere [in the copper water lines in the ceiling] .the bathroom wall situation, that's from moisture .old floors .wall damage .
Telephone interview with the Corporate Director of Plant Operations on 6/27/19 at 11:02 AM, the Corporate Director of Plant Operations was asked what environmental problems he had identified in the building. The Corporate Director of Plant Operations said that he started his position in January and stated, .We came down to look at .copper lines .had multiple saddle repair [pipe repair] clamps .pipe over the nurse station had a number of saddle clamp repairs, we made the conclusion that the pipe was reaching its end and deteriorating. The Corporate Director of Plant Operations was asked when he was made aware of problems. He stated, .the Maintenance Director told me about it in February .it [referring to the leaking pipes] wasn't a dire issue in February . The Corporate Director of Plant Operations was asked who monitors the work provided by the contracted Housekeeping Services. The Corporate Director of Plant Operations stated, .What I understand was that the Administrator will walk around and grade them and make adjustments from there. The Corporate Director of Plant Operations was asked how Corporate ensures the Administrator is doing that. The Corporate Director of Plant Operations stated, I don't have an answer for that. The Corporate Director of Plant Operations stated, I've been there twice. The Corporate Director of Plant Operations was asked if he noticed problems with housekeeping on those visits. The Corporate Director of Plant Operations stated, .didn't notice .